Overview
IOMod 16DI is a stand-alone Modbus (RTU), IEC 60870-5-101 and IEC60870-5-103 digital input controller. Designed to achieve a high technological look and compact fit on DIN rail (EN 60715), IOMod 16DI is used for industrial applications where digital signaling is used and robust communication is essential.
IOMod 16DI is an ideal solution for such applications as data acquisition, observation, control, process monitoring, testing, and remote measurement. It is controlled over Modbus, IEC 60870-5-101 or IEC60870-5-103 protocol, and can be connected in parallel with other Modbus, IEC 60870-5-101 or IEC60870-5-103 equipment in a multi-drop installation scheme as in any SCADA system.
When using IOMod 16DI with WCC Lite gateway it is possible to monitor/control the I/O signals over Ethernet LANs or 3G/4G(LTE)/GSM/GPRS networks. It is a powerful solution for remote monitoring and control, alarm management, and data logging of I/O’s on CloudIndustries.eu cloud platform.
Features
- 16 digital inputs
- Configurable active input signal polarity or input inversion
- Configurable SPI, DPI
- Pulse count and ON time count
- Galvanically isolated inputs
- Configuration over USB console
- Drag and Drop firmware upgrade over USB mass storage
- Modbus, IEC 60870-5-101 or IEC60870-5-103 communication over RS485
- Software selectable termination resistor on RS485
- LED indication for input and data transmission
- Easy connection with WCC Lite gateway and CloudIndustries.eu platform
System
- PC USB connection: Mini USB
- Input connectors: Screw terminal plug connector
Software
- Configuration: Over USB console
- Firmware upgrade: Over USB mass storage
Communication
- Communication standard: RS485
- Communication protocol: Modbus RTU, IEC 60870-5-101 and IEC60870-5-103
- Speed: 600 – 115200 baud
Specifications
Device data | |
Article number | IOMOD-16DI |
Product Description | 16 Digital input module |
Configuration software | IOMOD Utility, Serial console (putty)* |
Warranty | 2 years |
Inputs and functions | |
Digital inputs | 16 |
Input voltage | 12-24 VDC |
Input signal polarity | Configurable |
Input inversion | Configurable |
Input filter | Configurable (0..256000ms) |
Input counter | 16 (one per input) with a reset function |
Interface and communication | |
RS485 interface | ANSI/TIA/EIA-485-A-1998 |
Communication protocols | – Modbus RTU Slave; – IEC 60870-5-101 Slave; – IEC 60870-5-103 Slave. |
Baudrate | 600 – 115200 |
Parity | None, Even, Odd |
Terminating resistors | 120 Ohm (configurable) |
USB interface | |
Type | Mini USB |
Use | Configuration/Firmware upgrade |
Power supply | |
Auxiliary power supply | 9-33VDC (full range) |
Power consumption | 40mA @ 12VDC, 20mA @ 24 VDC |
Insulation voltage | 3 kV |
Operating conditions | |
Operating temperature | -40°C … 85°C |
Storage temperature | -40°C … 85°C |
Relative humidity | max. 95 % (non condensing) |
Protection class | IP20 |
Dimensions and installation instructions | |
Case height x width x depth | 119 x 17.5 x 101 mm |
Installation type | DIN Rail mounting |
Documentation
- Online documentation about IOMOD modules
- Brochures and Manuals to download
- Firmware and tools
- ISO downloads
Order
IOMOD-16DI – 16 Digital input module with IEC 60870-5-103, IEC 60870-5-101, or Modbus RTU Slave protocol
On request*:
ON REQUEST AVAILABLE MODULES WITH INPUT VOLTAGES 48VDC.
* – IOMOD devices 8DI8DO, 8AI, 4RTD, 16DI, 8DI4RO, HT with firmware versions v1.x supports only 1 protocol. To change protocol is required to change firmware. All types of firmware are accessible to all customers without any additional payment.