Overview
The Mini RTU series devices are made to fulfill Utilities and distribution grids needs in automation. Additionally, this product line is commonly used as control and monitoring equipment for renewable energy sources (solar, wind and hydro). Due to its modularity and variety of selectable modules and functions this series can be implemented for different applications from simple protocol conversion with only the WCC Lite to complex tele-control applications with implemented algorithms, mobile connectivity, and fault passage indicator functions.
The Mini RTU series devices have advanced RTU functions with additional unique functionality as data logger capabilities to collect internal measurements and events, data as time-series data and ability to securely transfer information into the Premise or Cloud based monitoring systems. The Mini RTU series supports networking functions (switch, VPN server/client, rules-based firewall, RESTful API) that allows to easily implement networking tasks on the RTU itself without any additional equipment and improve Cyber security.
Features
- Versatile communications including most of energy protocols;
- Expandable with I/O modules and modules not limited in RACK;
- Simple engineering with the integrated web interface and free configuration tools;
- Small for factor allows to fit into retrofit projects;
- Mechanical design for DIN-rail mounting;
- Wide operating temperature range -40°C … 75°C;
- Easy remote parametrisation via internet and VPN;
- Integrated programmable user programs;
- Integrated I/O intelligence independently behave without interaction with main CPU;
- Rich Cyber security features:
- BDEW white paper conformity;
- IPsec and IKE encryption
- IPsec and OpenVPN VPN client;
- Role-based access control (RBAC) for power system management;
- Radius support for remote user rights management;
- SSL (TLS) encryption for IEC 60870-5-104 and IEC 61850;
- https protocol;
- Firmware signature;
- Security syslog;
- Rules based Firewall;
Specifications
Device data | Description |
Article number | Mini RTU series |
Product description | Mini RTU series is combination of products including WCCLite as CPU, CLMOD as interface converters and IOMOD devices as I/O and FPI modules |
Configuration software | WCC Excel utility, Putty, Web browser |
Warranty | 2 years |
General | Main RTU features |
Functionality | Freely scalable RTU with included all supported protocols and functions for utilities, grid and renewables automation solutions. |
RTU functionality | – Reading Process events from the input/output modules. – Send commands to the output modules. – Communication with sub devices to collect events and execute commands. – Communicating with control systems and other IOT systems. – Handling the configuration via WEB Browser and Elseta configuration tools; – Monitor communication status with sub devices. – Sequence-of-Event (SOE). – Execute user scripts to enable custom automation and regulation algorithms. – Connectivity: LAN/WAN, Mobile (4G LTE), VPN. – Firewall (rules based). |
Data exchange | Mini RTU are able to support up to 16 host systems including hot-standby SCADA systems. Every IEC 60870-5 protocol can have shared or independent buffers of events and support multiple SCADA communication at the same time. |
Data collection | Mini RTU series supports collection of data up to 50 sub devices, e.g. IED’s, meters, IO’s, Inverters. Each sub device connected to mini RTU is supervised by RTU and shown status in diagnostic screen. |
PLC | Mini RTU series support: – distributed PLC based IEC 61499 standard; – Script execution engine (recommended) to write own programs based on LUA programming language. |
Data storage | RTU provide archive all data on non-volatile flash for events, measurements, counter values, security events. |
Time management | mini RTU series provides multilevel time management solution CPU supports NTP, IEC 60870, DNP3 time sync multi sourcing and IOMOD devices has time sync option with IEC 60870 protocol firmware. |
Time sync sources | Multi time sync options (priority based): – Internal RTC clock with battery basedmemory up to >15 years of life time; – NTP (Network Time Protocol) over TCP/IP; – IEC 60870-5 time sync support; – DNP3 time sync support; – IEC 61850 time sync support. |
Time sync precision | The time base operates with a time resolution of 1 ms. |
Communication interfaces | Interfaces for communication with IED’s, Meters, inverters, SCADA systems and etc. |
Independent Ethernet ports | 2x 10/100 Mbps 10/100Base-T compliance IEEE 802.3, IEEE 802.3u standards, supports auto MDI/MDIX |
Serial ports | 2x RS485 (Standard ANSI/TIA/EIA-485-A) |
Serial ports | 1x RS232 (Standard EIA/TIA-232-E) Switchable with RS485 port1 |
Mobile communication | Available only with integrated WCCLite version with mobile communication module |
Mobile technology support | 4G (LTE) – Cat 4 up to 150 Mbps, 3G – Up to 42 Mbps, 2G – Up to 236.8 kbps |
Dual SIM card support | 2 SIM cards, auto-switch cases: weak signal, data limit, no network, network denied, data connection fail |
Other mobile info | Signal strength (RSSI), SINR, RSRP, RSRQ, RSCP, IMSI, ICCID, Signal strength LED indicators, SMS receive/send, APN management. |
LED indication | To indicate traffic on interface every interface has independent LED indication on receive/send packet. |
Supported protocols | Host and sub device communication protocols |
IEC 60870 | IEC 60870-5-101 Master support IEC 60870-5-101 Slave support IEC 60870-5-103 Master support (WCCLite only) IEC 60870-5-103 Slave support (IOMOD modules only) IEC 60870-5-104 Master support IEC 60870-5-104 Slave support (KEMA Cert.) + IEC 62351 (parts -3) security standard is supported TLS encryption |
DNP3 | DNP3.0 TCP(LAN/WAN) Master support DNP3.0 TCP(LAN/WAN) Slave support DNP3.0 Serial Master support DNP3.0 Serial Slave support IEC 62351 (parts -3) security standard is supported TLS encryption |
Modbus | Modbus RTU Master support Modbus RTU Slave support Modbus ASCII Master support Modbus ASCII Slave support Modbus TCP Master support Modbus TCP Slave support |
IEC 61850-8-1 | Client (Master) support of Editions 1, 2, 2.1 – MMS client – Read services – Write services – Static data sets – Report Control blocks – Controls – Discovery Server (Slave) support of Editions 1, 2, 2.1 – MMS server – Read services – Write services – Static data sets – Report Control blocks – Controls – Discovery IEC 62351 (parts -3, -4, -5 and -6) security standard is supported for authentication and TLS encryption |
Meter protocols | M-bus Master support DLMS/COSEM master support IEC 62056-21 master support IEC 62056-31 master support |
Other protocols | MQTT, RESTful API |
Cyber security | Comply with BDEW white paper, IEC 62351 and general cyber security practices |
Secure access | Secure access to all services (HTTPS, SSH) |
RBAC | Role-based access protection with login and password IEC 62351 by security standard is supported. |
User administration | Local users administration with different access levels Central user administration via RADIUS |
Password complexity | Fully customisable password policy: – minimum password length, – maximum password lifetime, – usage of lower case characters, – upper case characters, – numeric, – special characters. |
Certificate storage | Internal Crypto Store for certificate management Import of certificates |
Input/Output modules | |
IOMOD 8DI4RO | 8x digital inputs and 4x relay outputs (NO) module |
Digital inputs | 8 |
Input voltage | 12-48VDC |
Input signal polarity | Yes, configurable |
Input inversion | Yes, configurable |
Input grouping | up to 4 groups DPI |
Relay outputs | 4 (normal open contact) |
Output current | <10 A (per output) |
Output voltage | 60VDC, 250VAC |
Output functions | Permanent or Pulse output |
Output pulse | Configurable in ms (0..60s) |
Output feedback time | Configurable in ms (0..60s) |
Output grouping | up to 2 groups DCO |
IOMOD 8DI8DO | 8x digital inputs and 8x digital outputs (transistor) module |
Digital inputs | 8 |
Input voltage | 12-24 VDC |
Input signal polarity | Yes, configurable |
Input inversion | Yes, configurable |
Input grouping | up to 4 groups DPI |
Digital outputs | 8 (open collector) |
Output current | <500mA (per output) |
Output voltage | 12..24VDC |
Output functions | Permanent or Pulse output |
Output pulse | Configurable in ms (0..60s) |
Output feedback time | Configurable in ms (0..60s) |
Output grouping | up to 4 groups DCO |
IOMOD 16DI | 16x digital inputs module |
Digital inputs | 16 |
Input voltage | 12-24 VDC |
Input signal polarity | Yes, configurable |
Input inversion | Yes, configurable |
Input filter | Yes, configurable (0..256000ms) |
Input counter | 16 (one per input) with reset function |
IOMOD 8AI | 8x analog inputs module |
Analog inputs | 8 configurable analog inputs |
Inputs resolution | 16 bit |
Channel-independent programmable input types | Voltage and current inputs |
Voltage input ranges | Bipolar: +-10.24V, +-5.12V, +-2.56V Unipolar: 10.24V, 5.12V |
Current input ranges | Bipolar: +-51.2mA, +-25.6mA, +-12.8mA Unipolar: 51.2mA, 25.6mA |
Overvoltage protection | +-20V |
IOMOD 4RTD | 4x temperature sensors module |
Analog inputs | 4 RTD (PT100 / PT1000) |
Input supports sensors | PT100 and PT1000 temperature RTD sensor |
Input connection | 2, 3 or 4 wires connection |
Temperature measurement range | -200 to 800 °C using platinum RTD sensors |
Accuracy | 0.5°C accuracy for all operating conditions |
IOMOD 4Cs4Vs | 4xCurrent 4xVoltage sensors module |
Analog inputs | 8x 16-bit resolution (Channel-independent) |
Current inputs | 4 |
Current inputs measurement range | 225 mV (IEC 60044-8) |
Current input impedance | 1 MΩ; < 170 pF |
Voltage inputs | 4 |
Voltage inputs measurement range | 3.25 V/√3 AC (IEC 60044-7) |
Voltage input impedance | 1 MΩ; < 170 pF |
Accuracy | 1% (for all channels) |
Frequency measurement range | 45..65 Hz |
Overvoltage protection | ±20V |
Power supply | |
Auxiliary power supply | 9-33VDC (full range) |
Insulation voltage | 3 kV |
Operating conditions | |
Operating temperature | -40°C … 55°C |
Storage temperature | -40°C … 85°C |
Relative humidity | max. 95 % (non condensing) |
Protection class | IP20 |
Dimensions | |
Installation type | DIN Rail mounting |
Case height x width x depth | WCCLite – 119 x 22.5 x 101 mm IOMOD – 119 x 17.5 x 101 mm |
Documentation
- Online documentation about IOMOD modules
- IOMOD Brochures and Manuals to download
- IOMOD Firmware and tools
- Online documentation about WCCLite
- WCCLite Brochures and Manuals to download
- WCCLite Firmware and tools
Order
WCCLite without modem – WCCLite without modem
WCCLITE 4G/3G/2G – WCC Lite v1.4 with 4G/3G/2G Modem
IOMOD-8DI8DO-IEC103 – 8 Digital inputs and 8 digital outputs module with IEC 60870-5-103 Slave protocol
IOMOD-16DI-IEC103 – 16 Digital input module with IEC 60870-5-103 Slave protocol
IOMOD-8AI-IEC103 – 8x analog input module with IEC 60870-5-103 Slave protocol
IOMOD-4RTD-IEC103 – 4xChannel PT100,PT1000 input module with IEC 60870-5-103 Slave protocol
IOMOD-4CS4VS – 4xCurrent 4xVoltage sensors module with IEC-101, IEC103, Modbus protocol support.
On request*:
IOMOD-8DI8DO-IEC101 – 8 Digital inputs and 8 digital outputs module with IEC 60870-5-101 Slave protocol
IOMOD-8DI8DO-Modbus – 8 Digital inputs and 8 digital outputs module with Modbus RTU Slave protocol
IOMOD-16DI-IEC101 – 16 Digital input module with IEC 60870-5-101 Slave protocol
IOMOD-16DI-Modbus – 16 Digital input module with Modbus RTU Slave protocol
IOMOD-8AI-IEC101 – 8x analog input module with IEC 60870-5-101 Slave protocol
IOMOD-8AI-Modbus – 8x analog input module with Modbus RTU Slave protocol
IOMOD-4RTD-IEC101 – 4xChannel PT100,PT1000 input module with IEC 60870-5-101 Slave protocol
IOMOD-4RTD-Modbus – 4xChannel PT100,PT1000 input module with Modbus RTU Slave protocol
* – IOMOD devices 8DI8DO, 8AI, 4RTD, 16DI, 8DI2RO, HT with firmware versions v1.x supports only 1 protocol. To change protocol is required to change firmware. All types of firmware are accessible to all customers without any additional payment.